Menu 21 − EtherNet/IP In Mappings


Parameter21.001  Input mapping parameter 1
Short descriptionSets input mapping parameter 1
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default10040
(Display: 0.10.040)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.002  Input mapping parameter 2
Short descriptionSets input mapping parameter 2
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default2001
(Display: 0.02.001)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.003  Input mapping parameter 3
Short descriptionSets input mapping parameter 3
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.004  Input mapping parameter 4
Short descriptionSets input mapping parameter 4
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.005  Input mapping parameter 5
Short descriptionSets input mapping parameter 5
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.006  Input mapping parameter 6
Short descriptionSets input mapping parameter 6
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.007  Input mapping parameter 7
Short descriptionSets input mapping parameter 7
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.008  Input mapping parameter 8
Short descriptionSets input mapping parameter 8
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.009  Input mapping parameter 9
Short descriptionSets input mapping parameter 9
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.010  Input mapping parameter 10
Short descriptionSets input mapping parameter 10
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.011  Input mapping parameter 11
Short descriptionSets input mapping parameter 11
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.012  Input mapping parameter 12
Short descriptionSets input mapping parameter 12
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.013  Input mapping parameter 13
Short descriptionSets input mapping parameter 13
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.014  Input mapping parameter 14
Short descriptionSets input mapping parameter 14
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.015  Input mapping parameter 15
Short descriptionSets input mapping parameter 15
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.016  Input mapping parameter 16
Short descriptionSets input mapping parameter 16
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.017  Input mapping parameter 17
Short descriptionSets input mapping parameter 17
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.018  Input mapping parameter 18
Short descriptionSets input mapping parameter 18
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.019  Input mapping parameter 19
Short descriptionSets input mapping parameter 19
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.


Parameter21.020  Input mapping parameter 20
Short descriptionSets input mapping parameter 20
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a source parameter for the data that will be transmitted to the PLC. The default value for the parameter is zero.