Menu 22 − EtherNet/IP Out Mappings

Parameter22.001  Output mapping parameter 1
Short descriptionSets output mapping parameter 1
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default6042
(Display: 0.06.042)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.002  Output mapping parameter 2
Short descriptionSets output mapping parameter 2
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default1021
(Display: 0.01.021)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.003  Output mapping parameter 3
Short descriptionSets output mapping parameter 3
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.004  Output mapping parameter 4
Short descriptionSets output mapping parameter 4
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.005  Output mapping parameter 5
Short descriptionSets output mapping parameter 5
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.006  Output mapping parameter 6
Short descriptionSets output mapping parameter 6
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.007  Output mapping parameter 7
Short descriptionSets output mapping parameter 7
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.008  Output mapping parameter 8
Short descriptionSets output mapping parameter 8
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.009  Output mapping parameter 9
Short descriptionSets output mapping parameter 9
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.010  Output mapping parameter 10
Short descriptionSets output mapping parameter 10
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.011  Output mapping parameter 11
Short descriptionSets output mapping parameter 11
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.012  Output mapping parameter 12
Short descriptionSets output mapping parameter 12
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.013  Output mapping parameter 13
Short descriptionSets output mapping parameter 13
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.014  Output mapping parameter 14
Short descriptionSets output mapping parameter 14
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.015  Output mapping parameter 15
Short descriptionSets output mapping parameter 15
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.016  Output mapping parameter 16
Short descriptionSets output mapping parameter 16
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.017  Output mapping parameter 17
Short descriptionSets output mapping parameter 17
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.018  Output mapping parameter 18
Short descriptionSets output mapping parameter 18
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.019  Output mapping parameter 19
Short descriptionSets output mapping parameter 19
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.


Parameter22.020  Output mapping parameter 20
Short descriptionSets output mapping parameter 20
Minimum0
(Display: 0.00.000)
Maximum499999
(Display: 4.99.999)
Default0
(Display: 0.00.000)
Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParamDecimal Places0
CodingRW, DE, PT, BU

This parameters defines a destination parameter for the data that will be transmitted from the PLC. The default value for the parameter is zero.